Fire Pump Pipe Size Calculator Icon

Fire Pump Pipe Sizing App

Summary: This app provides a visual representation of the minimum pipe sizes required per NFPA 20 table 4.26(a) for Centrifugal Fire Pumps. Correct application of the data obtained from the use of this program is the responsibility of the user. This software is not a substitute for technical knowledge of fire pumps and/or piping design.


NFPA 20 fire pump diagram with numbered components
# Component Min. size
1Suction3.5"
2Discharge3"
3Test header supply3"
4Flow meter3.5"
5Test header hose valves(1) 2.5"
6Main relief valve2"
7Relief valve discharge2.5"
8Circulation relief0.75"

NFPA 20 Fire Pump Diagram